CHAPTER 8: DNP COMMUNICATIONS DNP 3.0 PROTOCOL
PQM POWER QUALITY METER – INSTRUCTION MANUAL 8–15
72 024C
Phase B Current -
Maximum
1000ths of
nominal A
1 unit F1 3
73 024D
Phase C Current -
Maximum
1000ths of
nominal A
1 unit F1 3
74 024E
Neutral Current -
Maximum
1000ths of
nominal A
1 unit F1 3
75 024F
Current Unbalance -
Maximum
tenths of 1
percent
1 unit F1 3
76 0291 Voltage Van - Minimum
1000ths of
nominal V
1 unit F3 3
77 0293 Voltage Vbn - Minimum
1000ths of
nominal V
1 unit F3 3
78 0295 Voltage Vcn - Minimum
1000ths of
nominal V
1 unit F3 3
79 0297 Voltage Vab - Minimum
1000ths of
nominal V
1 unit F3 3
80 0299 Voltage Vbc - Minimum
1000ths of
nominal V
1 unit F3 3
81 029B Voltage Vca - Minimum
1000ths of
nominal V
1 unit F3 3
82 029D
Voltage Unbalance -
Minimum
0.1 x % 1 unit F1 3
83 029E
Voltage Van -
Maximum
1000ths of
nominal V
1 unit F3 3
84 02A0
Voltage Vbn -
Maximum
1000ths of
nominal V
1 unit F3 3
85 02A2 Voltage Vcn - Maximum
1000ths of
nominal V
1 unit F3 3
86 02A4
Voltage Vab -
Maximum
1000ths of
nominal V
1 unit F3 3
87 02A6 Voltage Vbc - Maximum
1000ths of
nominal V
1 unit F3 3
88 02A8 Voltage Vca - Maximum
1000ths of
nominal V
1 unit F3 3
89 02AA
Voltage Unbalance -
Maximum
0.1 x % 1 unit F1 3
Table 8–4: Point List for Analog Input/Output Change (Sheet 5 of 9)
POINT MOBUS
REG
DESCRIPTION UNIT /
VALUE
DEADBAND FORMAT
CODE
EVENT
CLASS
ASSIGNED
TO
see footnote explanations at the end of the table
Courtesy of NationalSwitchgear.com