8–16 PQM POWER QUALITY METER – INSTRUCTION MANUAL
DNP 3.0 PROTOCOL CHAPTER 8: DNP COMMUNICATIONS
90 030C
3 Phase Real Power -
Minimum
1000ths of
nominal W
1 unit F4 3
91 030E
3 Phase Reactive Power
Minimum
1000ths of
nominal
kvar
1 unit F4 3
92 0310
3 Phase Apparent
Power Minimum
1000ths of
nominal VA
1 unit F3 3
93 0312
3 Phase Power Factor -
Minimum
%1 unitF23
94 0313
3 Phase Real Power -
Maximum
1000ths of
nominal
1 unit F4 3
95 0315
3 Phase Reactive Power
Maximum
1000ths of
nominal
1 unit F4 3
96 0317
3 Phase Apparent
Power Maximum
1000ths of
nominal
1 unit F3 3
97 0319
3 Phase Power Factor -
Maximum
%1 unitF23
98 031A
Phase A Real Power -
Minimum
1000ths of
nominal
1 unit F4 3
99 031C
Phase A Reactive Power
Minimum
1000ths of
nominal
1 unit F4 3
100 031E
Phase A Apparent
Power Minimum
1000ths of
nominal
1 unit F3 3
101 0220
Phase A Power Factor -
Minimum
%1 unitF23
102 0321
Phase A Real Power -
Maximum
1000ths of
nominal
1 unit F4 3
103 0323
Phase A Reactive Power
Maximum
1000ths of
nominal
1 unit F4 3
104 0325
Phase A Apparent
Power Maximum
1000ths of
nominal
1 unit F3 3
105 0327
Phase A Power Factor
Maximum
%1 unitF23
106 0328
Phase B Real Power
Minimum
1000ths of
nominal
1 unit F4 3
107 032A
Phase B Reactive Power
Minimum
1000ths of
nominal
1 unit F4 3
Table 8–4: Point List for Analog Input/Output Change (Sheet 6 of 9)
POINT MOBUS
REG
DESCRIPTION UNIT /
VALUE
DEADBAND FORMAT
CODE
EVENT
CLASS
ASSIGNED
TO
see footnote explanations at the end of the table