CHAPTER 8: DNP COMMUNICATIONS DNP 3.0 PROTOCOL
PQM POWER QUALITY METER – INSTRUCTION MANUAL 8–17
108 032C
Phase B Apparent
Power Minimum
1000ths of
nominal
1 unit F3 3
109 032E
Phase B Power Factor
Minimum
%1 unitF23
110 032F
Phase B Real Power
Maximum
1000ths of
nominal
1 unit F4 3
111 0331
Phase B Reactive Power
Maximum
1000ths of
nominal
1 unit F4 3
112 0333
Phase B Apparent
Power Maximum
1000ths of
nominal
1 unit F3 3
113 0335
Phase B Power Factor
Maximum
%1 unitF23
114 0336
Phase C Real Power
Minimum
1000ths of
nominal
1 unit F4 3
115 0338
Phase C Reactive Power
Minimum
1000ths of
nominal
1 unit F4 3
116 033A
Phase C Apparent
Power - Minimum
1000ths of
nominal
1 unit F3 3
117 033C
Phase C Power Factor
Minimum
%1 unitF23
118 033D
Phase C Real Power
Maximum
1000ths of
nominal
1 unit F4 3
119 033F
Phase C Reactive Power
Maximum
1000ths of
nominal
1 unit F4 3
120 0341
Phase C Apparent
Power Maximum
1000ths of
nominal
1 unit F3 3
121 0343
Phase C Power Factor
Maximum
%1 unitF23
122 040A
Phase A Current
Demand Maximum
1000ths of
nominal
1 unit F1 3
123 040B
Phase B Current
Demand Maximum
1000ths of
nominal
1 unit F1 3
124 040C
Phase C Current
Demand Maximum
1000ths of
nominal
1 unit F1 3
125 040D
Neutral Current
Demand Maximum
1000ths of
nominal
1 unit F1 3
Table 8–4: Point List for Analog Input/Output Change (Sheet 7 of 9)
POINT MOBUS
REG
DESCRIPTION UNIT /
VALUE
DEADBAND FORMAT
CODE
EVENT
CLASS
ASSIGNED
TO
see footnote explanations at the end of the table