8–18 PQM POWER QUALITY METER – INSTRUCTION MANUAL
DNP 3.0 PROTOCOL CHAPTER 8: DNP COMMUNICATIONS
126 040E
3 Phase Real Power
Dmd Max
1000ths of
nominal
1 unit F4 3
127 0410
3 Phase React Power
Dmd Max
1000ths of
nominal
1 unit F4 3
128 0412
3 Phase Apparent
Power Dmd Max
1000ths of
nominal
1 unit F3 3
129 0441 Frequency Minimum 0.01 x Hz .01 Hz F1 3
130 0442 Frequency Maximum 0.01 x Hz .01 Hz F1 3
131 0482
Phase A Current THD -
Maximum
0.1 x % 1 unit F1 3
132 0483
Phase B Current THD -
Maximum
0.1 x % 1 unit F1 3
133 0484
Phase C Current THD -
Maximum
0.1 x % 1 unit F1 3
134 0485
Neutral Current THD -
Maximum
0.1 x % 1 unit F1 3
135 0486
Voltage Van THD -
Maximum
0.1 x % 1 unit F1 3
136 0487
Voltage Vbn THD -
Maximum
0.1 x % 1 unit F1 3
137 0488
Voltage Vcn THD -
Maximum
0.1 x % 1 unit F1 3
138 0489
Voltage Vab THD -
Maximum
0.1 x % 1 unit F1 3
139 048A
Voltage Vbc THD -
Maximum
0.1 x % 1 unit F1 3
140 048B Reserved ----- ----- --- ---
141 04C8 ADC Reference - 20 units F1 2
142 04C9 Power Loss Fine Time 10 ms 1 unit F1 2
143 04CA
Power Loss Coarse
Time
0.1 min. 1 unit F1 2
144 04CB Current Key Press - 1 unit
F8
2
145 04CC
Internal Fault Error
Code
-1 unitF1082
Table 8–4: Point List for Analog Input/Output Change (Sheet 8 of 9)
POINT MOBUS
REG
DESCRIPTION UNIT /
VALUE
DEADBAND FORMAT
CODE
EVENT
CLASS
ASSIGNED
TO
see footnote explanations at the end of the table