4–22 PQM POWER QUALITY METER – INSTRUCTION MANUAL
S2 SYSTEM SETUP CHAPTER 4: PROGRAMMING
If A AND B ONLY, A AND C ONLY, or A ONLY connection is selected, the 
neutral sensing must be accomplished with a separate CT.
• PHASE CT PRIMARY: Enter the primary current rating of the phase current 
transformers. All three phase CTs must have the same rating. For example, if 500:5 CTs 
are used, the 
PHASE CT PRIMARY value is entered as 500. The PHASE CT PRIMARY 
factory default is OFF. While set to OFF, the PQM is forced to an alarm state as a safety 
precaution until a valid CT value is entered. Ensure that the CT is connected to the 
correct 1 A or 5 A terminals to match the CT secondary.
• NEUTRAL CURRENT SENSING: Neutral current sensing can be accomplished by using 
a separate external CT connection or by calculations. Select SEPARATE CT when using 
an external CT. If CALCULATED is selected, the PQM calculates the neutral current 
using the vector sum of I
a
 + I
b
 + I
c
 = I
n
. If a residual connection is required using the 
PQM internal CT, the neutral CT primary must be the same as the phase CT primary to 
ensure correct readings.
• NEUTRAL CT PRIMARY: This message is visible only if the 
NEUTRAL CURRENT 
SENSING
 setpoint is set to SEPARATE CT. Enter the CT primary current. For example, if 
a 50:5 CT is installed for neutral sensing enter 
50. One amp CTs can also be used for 
neutral sensing.
• VT WIRING: Enter the VT connection of the system in this setpoint. The three possible 
selections are Wye, Delta and Single Phase.
If the system to be measured is a Wye connection, the selections are 4 WIRE WYE 
DIRECT, 4 WIRE WYE (3 VTs), and 4 WIRE WYE (2 VTs). The 4 WIRE WYE DIRECT value is 
used for systems that are 600 V or less and directly connected to the PQM. The 
VT 
NOMINAL SECONDARY VOLTAGE
 setpoint is replaced by NOMINAL DIRECT INPUT 
VOLTAGE
. With external VTs (depending upon how many external VTs are used) 4 
WIRE WYE (3 VTs) or 4 WIRE WYE (2 VTs) must be selected. Note that when using the 4 
WIRE WYE (2 VTs) value, only two voltages are measured; the third voltage is 
calculated on the assumption that V
an
 + V
bn
 + V
cn
 = 0. This assumption is valid only for 
balanced system voltages.
If the system to be measured is a Delta connection, the values are 3 WIRE DIRECT and 
3 WIRE DELTA (2 VTs). The 3 WIRE DIRECT value should be used for systems that are 
600 V or less and directly connected to the PQM. With external VTs, 3 WIRE DELTA (2 
VTs) must be selected.
The PQM accepts input voltages from 0 to 600 V AC between any two of the voltage 
terminals (V
1
, V
2
, V
3
, and V
n
). These inputs can be directly connected or supplied via 
external VTs. External VTs are required for input voltages greater than 600 V AC (line-
to-line). When measuring line-to-line quantities using inputs V
1
, V
2
 and V
3
, ensure that 
the voltage common input V
n
 is grounded. This input is used as a reference for 
measuring the voltage inputs.
All connections to the PQM voltage inputs should be connected using HRC 
fuses rated at 2 amps to ensure adequate interrupting capacity.
• VT RATIO: Enter the voltage transformer ratio. All three voltage inputs must be of the 
same rating. For example, if 4200:120 VTs are used, the 
VT RATIO should be 4200 /
NOTE
NOTE
Courtesy of NationalSwitchgear.com