CHAPTER 4: PROGRAMMING S2 SYSTEM SETUP
PQM POWER QUALITY METER – INSTRUCTION MANUAL 4–23
120 = 35.0:1. This setpoint is not visible if VT WIRING is set to 3 WIRE DIRECT, 4 WIRE 
DIRECT, or SINGLE PHASE DIRECT.
• VT NOMINAL SECONDARY VOLTAGE: Enter the nominal secondary of the VTs. If the 
voltage inputs are directly connected, enter the nominal system voltage that will be 
applied to the PQM. This setpoint is not visible if the 
VT WIRING is set to 3 WIRE 
DIRECT, 4 WIRE DIRECT, or SINGLE PHASE DIRECT. This value is used to scale an analog 
output that is assigned to display voltage as a percentage of nominal.
• NOMINAL DIRECT INPUT VOLTAGE: This setpoint is displayed only if 
VT WIRING is 
selected as a direct connection. The nominal direct input voltage must be entered in 
this message. This value will be used to scale an analog output that is assigned to 
display voltage as a percentage of nominal.
• NOMINAL SYSTEM FREQUENCY: Enter the nominal system frequency. The PQM 
measures frequency from the V
an
 voltage and adjusts its internal sampling to best fit 
the measured frequency. If the V
an
 input is unavailable, the PQM will assume the 
frequency entered here.