GE Multilin T60 Transformer Protection System B-81
APPENDIX B B.4 MEMORY MAPPING
B
EA58 PMU 1 Voltage Trigger High Volt 0.75 to 1.75 pu 0.001 F001 1200
EA59 PMU 1 Voltage Trigger Pkp Time 0 to 600 s 0.01 F001 10
EA5A PMU 1 Voltage Trigger Dpo Time 0 to 600 s 0.01 F001 100
EA5B PMU 1 Voltage Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
EA61 PMU 1 Voltage Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EA62 PMU 1 Voltage Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit Current Trigger (Read/Write Setting
EAA4 PMU 1 Current Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EAA5 PMU 1 Current Trigger Pickup 0.1 to 30 pu 0.001 F001 1800
EAA6 PMU 1 Current Trigger Pkp Time 0 to 600 s 0.01 F001 10
EAA7 PMU 1 Current Trigger Dpo Time 0 to 600 s 0.01 F001 100
EAA8 PMU 1 Current Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
EAAE PMU 1 Current Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EAAF PMU 1 Current Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit Frequency Trigger (Read/Write Setting)
EAEC PMU 1 Frequency Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EAED PMU 1 Frequency Trigger Low Frequency 20 to 70 Hz 0.01 F001 4900
EAEE PMU 1 Frequency Trigger High Frequency 20 to 70 Hz 0.01 F001 6100
EAEF PMU 1 Frequency Trigger Pickup Time 0 to 600 s 0.01 F001 10
EAF0 PMU 1 Frequency Trigger Dropout Time 0 to 600 s 0.01 F001 100
EAF1 PMU 1 Frequency Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
EAF7 PMU 1 Frequency Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EAF8 PMU 1 Frequency Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
EB3A PMU 1 df/dt Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EB3B PMU 1 df/dt Trigger Raise 0.1 to 15 Hz/s 0.01 F001 25
EB3C PMU 1 df/dt Trigger Fall 0.1 to 15 Hz/s 0.01 F001 25
EB3D PMU 1 df/dt Trigger Pkp Time 0 to 600 s 0.01 F001 10
EB3E PMU 1 df/dt Trigger Dpo Time 0 to 600 s 0.01 F001 100
EB3F PMU 1 df/dt Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
EB45 PMU 1 df/dt Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EB46 PMU 1 df/dt Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit Power Trigger (Read/Write Setting)
EB88 PMU 1 Power Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EB89 PMU 1 Power Trigger Active 0.25 to 3 pu 0.01 F001 1250
EB8A PMU 1 Power Trigger Reactive 0.25 to 3 pu 0.01 F001 1250
EB8B PMU 1 Power Trigger Apparent 0.25 to 3 pu 0.01 F001 1250
EB8C PMU 1 Power Trigger Pkp Time 0 to 600 s 0.01 F001 10
EB8D PMU 1 Power Trigger Dpo Time 0 to 600 s 0.01 F001 100
EB8E PMU 1 Power Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0
EB94 PMU 1 Power Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EB95 PMU 1 Power Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit Calibration (Read/Write Setting)
EBDC PMU Va Calibration Angle -5 to 5 ° 0.05 F002 0
EBDD PMU Va Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBDE PMU Vb Calibration Angle -5 to 5 ° 0.05 F002 0
EBDF PMU Vb Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBE0 PMU Vc Calibration Angle -5 to 5 ° 0.05 F002 0
EBE1 PMU Vc Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBE2 PMU Vx Calibration Angle -5 to 5 ° 0.05 F002 0
EBE3 PMU Vx Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBE4 PMU Ia Calibration Angle -5 to 5 ° 0.05 F002 0
EBE5 PMU Ia Calibration Magnitude 95 to 105 % 0.1 F002 1000
EBE6 PMU Ib Calibration Angle -5 to 5 ° 0.05 F002 0
Table B–10: MODBUS MEMORY MAP (Sheet 73 of 74)