EasyManua.ls Logo

gefran ADV200

gefran ADV200
286 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ADV200 Functions description and parameters list 161
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.20 4550SpdRefLossthreshold rpm INT16 100 0 CALCI RW FVS
Setting of the threshold below which the speed reference loss alarm SpdRefLoss occurs.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.21 4552SpdRefLossactivity ENUM Ignore 0 4 RW FVS
Setting of the behaviour of the drive in case of a speed reference loss alarm SpdRefLoss. This alarm indicates
that the difference between the speed regulator reference and the actual motor speed is more than 100 rpm.
This alarm must be disabled (= 0 Ignore) when parameter 556 Controlmodeselect is set to Torque (0) or
when parameter 2354 is set to a value other than zero.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.22 4554SpdRefLossholdoff ms UINT16 1000 0 10000 RW FV_
Setting of the delay between the signalling of the speed reference loss alarm condition SpdRefLoss and ena-
bling of the alarm. If an alarm condition occurs, the drive will wait for the set time before enabling the alarm. If
the alarm is removed within the set time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.23 4560SpdFbkLossactivity ENUM Disable 0 4 RW FV_
Setting of the behaviour of the drive in case of a speed feedback loss alarm SpdFbkLoss. This alarm indicates
the loss of the encoder feedback signals.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.24 4562SpdFbkLossholdoff ms UINT16 200 0 10000 RW FVS
Setting of the delay between the signalling of the speed feedback loss alarm condition SpdFbkLoss and the
enabling of the alarm. If an alarm condition occurs, the drive will wait for the set time before enabling the alarm.
If the alarm is removed within the set time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.25 4564SpdFbkLossthreshold rpm INT16 100 5 CALCI RW FVS
For SE (single ended) encoders and with parameters 2110 or 5110 = (3) Control A-B-SE.
The Speedfbkloss[22] alarm control is enabled when the speed reference is higher than the value set in this
parameter
If using incremental digital encoders in single-ended mode, this parameter sets the limit above which the drive
executes the action set with parameter 4560 SpdFbkLossactivity.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.26 4570Driveovldactivity ENUM Ignore 0 4 ERW FVS
Setting of the behaviour of the drive in case of a drive overload alarm Driveovld. This alarm indicates that the
drive overload threshold has been reached.

Table of Contents

Other manuals for gefran ADV200

Related product manuals