ADV200 Functions description and parameters list 163
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.33 4604InAirrestarttime ms UINT16 1000 120 30000 ERW FVS
Setting of the time within which the IntakeairOT[11]alarm must be reset in order to perform automatic re-
start.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.34 4606InAirholdoff ms UINT16 10000 0 30000 ERW FVS
Setting of the delay between the signalling of the intake air overtemperature alarm IntakeairOT[11] and ena-
bling of the alarm. If an alarm condition occurs, the drive will wait for the set time before enabling the alarm. If
the alarm is removed within the set time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.35 4610Desatrestart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the desaturation alarm Desat. This alarm indicates a short circuit between
the motor phases or on the power bridge.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.36 4612Desatrestarttime ms UINT16 2000 1000 10000 ERW FVS
Setting of the time within which the Desaturation alarm must be reset in order to perform automatic restart.
(Time with alarm signal active + 1000 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.37 4620IOverCrestart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the drive overcurrent alarm. This alarm indicates an overcurrent (or short
circuit between phases or towards the ground).
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.38 4622IOverCrestarttime ms UINT16 2000 1000 10000 ERW FVS
Setting of the time within which the Overcurrent alarm must be reset in order to perform automatic restart.
(Time with alarm signal active + 1000 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.39 4630OverVrestart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the overvoltage alarm. This alarm indicates an overvoltage on the intermedi-
ate circuit (DC link)
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.40 4632OverVrestarttime ms UINT16 2000 1000 10000 ERW FVS
Setting of the time within which the Overvoltage alarm must be reset in order to perform automatic restart.
(Time with alarm signal active + 1000 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.41 4640UnderVrestart ENUM Enable 0 1 ERW FVS
Enabling of automatic restart after the undervoltage alarm. This alarm indicates an undervoltage on the inter-