www.gemu-group.com38 / 56GEMÜ 1235 / 1236
24V, 3S, 4S
7 Technical data
7 Technical data
7.1 Temperature
Ambient temperature: -10 — 70 °C
Storage temperature: -20 — 70 °C
7.2 Product compliance
RoHS Directive: 2011/65/EU
Machinery Directive: 2006/42/EC
EMC Directive: 2014/30/EU
Interference resistance: DIN EN 61000-6-2 (Nov. 2019)
Interference emission: DIN EN 61000-6-3
SIL: Product description: Electrical position indicator GEMÜ 1235_1236
Device type: B
Valid software version: V1.0.0.4
Safety function: The safety function is defined as a High (24 V DC) signal
at pin5 (device version 3S/4S) and at pin 4 (device ver-
sion 3E/4E), if the current position of the integrated travel
sensor is smaller than the switch point CLOSED (default
setting 12%).
HFT (Hardware Fault Tolerance): 0
MTTR (Mean Time To Restoration): 24 hours
MTBF (Mean Time Between Failures): 346 years
Further information, see SIL safety manual
UL listed for Canada and USA
Certificate: E515574
7.3 Mechanical data
Installation position: Optional
Weight: Travel length code 030: 115g
Travel length code 050: 138g
Travel length code 075: 160g
Protection class: IP 67
Travel sensor:
Travel sensor version Code
Code 030 Code 050 Code 075
Minimum stroke: 2.0 mm 3.5 mm 5.0 mm
Maximum stroke: 30.0 mm 50.0 mm 75.0 mm
Hysteresis: 0.2 mm 0.4 mm 0.5 mm
Accuracy: 0.2% Full Scale
7.4 Operating conditions
Ambient conditions: Use in indoor spaces
(only relevant for UL)