48 GMC-I Messtechnik GmbH
18 Characteristic Values
Func-
tion
Measured
Quantity
Display Range
Reso-
lution
Input
Impedance/
Test Current
Measuring Range Nominal Values
Measuring
Uncertainty
Intrinsic
Uncertainty
Connections
Plug
Insert
1)
2-Pole
Adapter
3-Pole
Adapter
Probe
Clamps
WZ12C Z3512A
MFLEX
P300
U
U
L-PE
U
N-PE
0 ... 99.9 V 0.1 V
5 M
90 ... 600 V
1)
U
N
= 120/230/
400/500 V
f
N
= 16
2
/
3
/50/
60/200/400 Hz
(2% rdg.+5d) (1% rdg.+5d)
lll
100 ... 600 V 1 V (2% rdg.+1d) (1% rdg.+1d)
f
15.0 ... 99.9 Hz
100 ... 999 Hz
0.1 Hz
1 Hz
15.4 ... 420 Hz (0.2% rdg.+1d) (0.1% rdg.+1d)
U
3~
0 ... 99.9 V
100 ... 600 V
0.1 V
1 V
90 ... 600 V
(3% rdg.+5d)
(3% rdg.+1d)
(2% rdg.+5d)
(2% rdg.+1d)
l
U
PROBE
0 ... 99.9 V
100 ... 600 V
0.1 V
1 V
0 ... 600 V
(2% rdg.+5d)
(2% rdg.+1d)
(1% rdg.+5d)
(1% rdg.+1d)
l
U
L-N
0 ... 99.9 V
100 ... 600 V
0.1 V
1 V
90 ... 600 V
1)
(3% rdg.+5d)
(3% rdg.+1d)
(2% rdg.+5d)
(2% rdg.+1d)
ll
I
N
I
F
U
IN
0 ... 70.0 V 0.1 V 0.3 · I
N
5 ... 70 V
U
N
= 120/230 V
f
N
= 50/60 Hz
U
L
= 25/50 V
I
N
= 10/30/
100/300/500
mA
U
N
1) 2)
= 400 V
+10% rdg.+1d
+1% rdg.–1d ...
+9% rdg.+1d
ll
l
optio
nal
R
E
/ I
N
= 10 mA 10 ... 6.51 k 10
calculated value
from
U
IN
/
I
N
R
E
/ I
N
= 30 mA
3 ... 999
1 k ... 2.17 k
3
10
R
E
/ I
N
= 100 mA 1 ... 651 1
R
E
/ I
N
= 300 mA
0.3 ... 99.9
100 ... 217
0.3
1
R
E
/ I
N
= 500 mA
0.2 ... 9.99
100 ... 130
0.2
1
I
/ I
N
= 10 mA 3.0 ... 13.0 mA
0.1 mA
3.0 ... 13.0 mA 3.0 ... 13.0 mA
(5% rdg.+1d) (3.5% rdg.+2d)
I
/ I
N
= 30 mA 9.0 ... 39.0 mA 9.0 ... 39.0 mA 9.0 ... 39.0 mA
I
/ I
N
= 100 mA 30 ... 130 mA 1 mA 30 ... 130 mA 30 ... 130 mA
I
/ I
N
= 300 mA 90 ... 390 mA 1 mA 90 ... 390 mA 90 ... 390 mA
I
/ I
N
= 500 mA 150 ... 650 mA 1 mA 150 ... 650 mA 150 ... 650 mA
U
I
/ U
L
= 25 V 0 ... 25.0 V
0.1 V wie I
0 ... 25.0 V
+10% rdg.+1d
+1% rdg.–1d ...
+9% rdg.+1 d
U
I
/ U
L
= 50 V 0 ... 50.0 V 0 ... 50.0 V
t
A
/ I
N
0 ... 1000 ms 1 ms 1.05 · I
N
0 ... 1000 ms
4 ms 3 ms
t
A
/ 5 · I
N
0 ... 40 ms 1 ms 5 · I
N
0 ... 40 ms I
N
= 10/30 mA
Z
L-PE
Z
L-N
Z
L-PE
(full waves)
Z
L-N
0 ... 999 m
1.00 ... 9.99
1 m
0.01
0.65 ... 4.0 A
0.15 ... 0.49
0.50 ... 0.99
1.00 ... 9.99
U
N
= 120/230 V
U
N
= 400 V
1)
/
500 V at Z
L-PE
f
N
= 50/60 Hz
(10% rdg.+ 30d)
(10% rdg.+ 30d)
(5% rdg.+ 3d)
(5% rdg.+30d)
(4% rdg.+30d)
(3% rdg.+3d)
l
l
Z
L-PE
Z
L-PE
DC+
0.25 ... 0.99
1.00 ... 9.99
(18% rdg.+30d)
(10% rdg.+3d)
(6% rdg.+50d)
(4% rdg.+3d)
I
K
0 A ... 999 A
1.00 kA ... 9.99 kA
10.0 kA ... 50.0 kA
1 A
10 A
100 A
120 (108 ... 132) V
230 (196 ... 253) V
400 (340 ... 440) V
calculated value from Z
L-PE
Z
L-PE
(15 mA)
0.5 ... 9.99 0.01 only display range
10.0 ... 99.9
100 ... 999
0.1
1
15 mA
10 ... 100
100 ... 1000
U
N
= 120/230 V
f
N
= 50/60 Hz
(10% v.M.+10D)
(8% v.M.+2D)
(2% v.M.+2D)
(1% v.M.+1D)
I
K
(15 mA)
100 ... 999 mA
0.00 ... 9.99 A
10.0 ... 99.9 A
1 mA
0.01 A
0.1 A
calcul. value depends
on U
N
and Z
L-PE
:
I
K
=U
N
/10...1000
calculated value from Z
L-PE
(15 mA):
I
K
= U
N
/Z
L-PE
(15 mA)
R
E
R
E
(with probe)
[R
E
(without probe)
values as Z
L-PE
]
0 ... 999 m
1.00 ... 9.99
10.0 ... 99.9
100 ... 999
1 k ...9.99 k
1 m
0,01
0,1
1
0.01 k
0.65 ... 3.4 A
0.65 ... 3.4 A
0.65 ... 3.4 A
400 mA
40 mA
4 mA
0.15 ... 0.49
0.50 ... 0.99
1.0 ...9.99
10 ...99.9
100 ...999
1 k ...9.99 k
U
N
= 120/230 V
U
N
= 400 V
1)
f
N
= 50/60 Hz
(10% rdg.+30d)
(10% rdg.+30d)
(5% rdg.+3d)
(10% rdg.+3d)
(10% rdg.+3d)
(10% rdg.+3d)
(5% rdg.+30d)
(4% rdg.+30d)
(3% rdg.+3d)
(3% rdg.+3d)
(3% rdg.+3d)
(3% rdg.+3d)
ll l
R
E
DC+
0 ... 999 m
1.00 ... 9.99
1 m
0,01
0.65 ... 3.4A
+ 1.25 A DC
0.25 ... 0.99
1.00 ... 9.99
U
N
= 120/230 V
f
N
= 50/60 Hz
(18% rdg.+ 30d)
(10% rdg. + 3d)
(6% rdg.+50D)
(4% v.M.+3D)
U
E
0 ... 253 V 1 V calculated value
R
E
Sel
clip
R
E
0 ... 999
1 m...
1
0.65 ... 3.4 A 0.25 ... 300 
5)
see R
E
(20% rdg.+ 20 D)
(15% rgd.+ 20 d)
l
l
R
E
DC+ 0 ... 999
1 m...
1
U
N
= 120/230 V
f
N
= 50/60 Hz
(22% v.M.+20 D)
(15% rdg.+ 20 d)
EX-
TRA
Z
ST
0 ... 30 M 1 k
2.3 mA at 230
V
10 k ... 199 k
200 k ... 30 M
U
0
= U
L-N
(20% rdg.+2d)
(10% rdg.+2d)
(10% rdg.+3d)
(5% rdg.+3d)
R
INS
R
INS
. R
E INS
1 ... 999 k
1.00 ... 9.99 M
10.0 ... 49.9 M
1 k
10 k
100 k
I
K
= 1.5 mA 50 k... 500 M
U
N
= 50 V
I
N
= 1 mA
krange
(5% rdg.+10d)
Mrange
(5% rdg.+1d)
krange
(3% rdg.+10d)
Mrange
(3% rdg.+1d)
ll
1 ... 999 k
1.00 ... 9.99 M
10.0 ... 99.9 M
1 k
10 k
100 k
U
N
= 100 V
I
N
= 1 mA
1 ... 999 k
1.00 ... 9.99 M
10.0 ... 99.9 M
100 ... 200 M
1 k
10 k
100 k
1 M
U
N
= 250 V
I
N
= 1 mA
1 ... 999 k
1.00 ... 9.99 M
10.0 ... 99.9 M
100 ... 500 M
1 k
10 k
100 k
1 M
U
N
= 500 V/
1000 V
I
N
= 1 mA
U 25 ... 1200 V– 1 V 25 ... 1200 V (3% rdg.+1d)
(1.5% rdg.+1d)
R
LO
R
LO
0.01 ... 9.99
10.0 ... 99.9
10 m
100 m
I
m
200 mA 0.1 ... 6 U
0
= 4.5 V (4% rdg.+2d) (2% rdg.+2d)
l

Table of Contents

Other manuals for Gossen MetraWatt PROFITEST MBASE MTECH

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gossen MetraWatt PROFITEST MBASE MTECH and is the answer not in the manual?

Gossen MetraWatt PROFITEST MBASE MTECH Specifications

General IconGeneral
BrandGossen MetraWatt
ModelPROFITEST MBASE MTECH
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals