EasyManuals Logo

Grant Vortex VTXBH15/26 User Manual

Grant Vortex VTXBH15/26
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
! NOTE !
If the exible liners must pass around an o󰀨set inside
the chimney, deduct two metres of straight ue length to
compensate for this.
The Grant Red system exible stainless steel liner is directional.
The arrows marked on the inner liner MUST be pointing vertically
upwards, following the direction of the ue gases. Failure to
comply with this instruction could lead to a leakage of condensate
from the ue liner.
Flue extensions cannot be cut, use adjustable extensions where
required.
Three types of locking band are supplied with the kit, as follows
(Refer to Figure 9-9):
Type 1. A white painted band - for connecting the white
painted ue sections that butt together, i.e. the joints with the
starter section and the rigid/exible adaptor.
! NOTE !
Two of this type of locking band are supplied in the kit.
Refer to Figure 9-9.
A single locking band of this type is supplied with every
additional elbow, extension kit or adjustable extension kit
used.
Type 2. A white painted band - to cover the sliding joint on
the white painted adjustable (telescopic) section.
! NOTE !
The locking band for the adjustable section is labelled for
easy identication.
A single locking band of this type is supplied with every
additional adjustable extension kit used.
Type 3. An unpainted stainless steel band - to secure the
outer of the two stainless steel ue liners to the white painted
rigid/exible adaptor.
The ue kit includes a Black coated terminal with upstand and is
designed to be xed (using the screws provided) to the top of a
masonry chimney.
The ue system may be o󰀨set using 45° elbows (product code:
ELBK2145/90 models up to 26 kW output).
No more than a maximum of four elbows should be used per
system.
EXTERNAL BALANCED FLUE
(GREEN SYSTEM)
Where it is not practical to use a low level (Yellow system) or
internal high level/vertical (White system) balanced ue, the
boiler can be tted with an external vertical/high level ue (Green
system).
See Figure 9-10.
The Starter kit ts to the boiler in the same way as a low level
balanced ue (Yellow system) and the external Tee allows the
connection of a twin wall insulated ue pipe and a combustion air
inlet - providing a room sealed ue system.
The external system can terminate at either high level or vertically
(above roof level) as required.
Up to three 45° elbows can be used in the vertical direction to
o󰀨set the ue around obstacles.
See Figure 9-10.
The minimum dimensions for locating the terminal from building
features (windows, doors, etc.) are shown in Figure 9-13.
The terminal must be positioned so as to avoid products of
combustion accumulating in stagnant pockets around the
buildings or entering into buildings. Care should be taken that the
plume from condensed ue gases does not cause a nuisance.
The components listed on the following page for the external ue
(Green system) components are available from Grant UK.
Section 9: Flue System and Air Supply Page 31
FLEXIBLE VERTICAL BALANCED FLUE (RED
SYSTEM)
Boiler
Flexible outer stainless steel liner
Terminal
Terminal upstand
Top plate
Support clamp
Rigid/flexible adaptor
Starter section
Telescopic flue (lower)
Telescopic flue (upper)
Locking band for
adjustable joint section
(Type 2)
Connector
Stainless Steel
Locking band
(Type 3)
Locking band
(Type 1)
Locking band
(Type 1)
Elbow, extension
and adjustable extension
from 'White' system
Flexible inner
stainless steel liner
The inner flue
liner is directional
(see Section 9.4)
Note:
Figure 9-9: Red system balanced ue (15-26 only)
This is a exible vertical balanced ue system (for the 15-26
models only) designed to be tted inside an existing masonry
chimney. See Figure 9-9.
It basically consists of three sections:
Concentric white painted ue pipe connected to the boiler.
The vertical concentric exible ue consists of a exible
stainless steel inner ue liner (directional) inside a exible
stainless steel outer ue liner.
Terminal assembly for chimney top mounting.
The ue pipe seals are factory tted and must be lubricated with
the lubricant supplied before assembly.
The Red system is supplied as a separate kit. Flue extensions
and 45° elbows from the White system may be used to extend the
ue between the boiler and the exible section of the system.
The maximum vertical straight length of ue, from the top of the
boiler to the top of the terminal, is 20 metres – using no more than
four 45° elbows. Deduct 1 metre of straight ue length for every
elbow used.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grant Vortex VTXBH15/26 and is the answer not in the manual?

Grant Vortex VTXBH15/26 Specifications

General IconGeneral
BrandGrant
ModelVortex VTXBH15/26
CategoryBoiler
LanguageEnglish

Related product manuals