44
No Short Name Full Name
58 HS-IPM-PFC over-TC2
Heat sink or IPM or PFC over-temperature of
compressor 2
59 HS-IPM-PFC SEC2
Heat sink or IPM or PFC temperature sensor error
of compressor 2
60
Charging circuit-EC2 Charging circuit error of compressor 2
61
DC under-voltageF1
DC busbar under-voltage or voltage drop error of
fan 1
62
DC over-voltageF1
DC busbar over-voltage or voltage drop error of
fan 1
63 IPM errorF1 IPM failure of fan 1
64
Startup failureF1 Startup failure of fan 1
65
Dri-Mod resettingF1 Drive module resetting of fan 1
66 Fan-Over-currentF1 Over-current of fan 1
67 Current circuit SEF1
Current sensing circuit error or current sensor
error of fan 1
68
DesynchronizingF1 Desynchronizing of fan 1
69 Fan-Dri-Comm-EF1 Communication error to the drive of fan 1
70 HS-IPM-PFC over-TF1
Heat sink or IPM or PFC over-temperature of fan
1
71 HS-IPM-PFC SEF1
Heat sink or IPM or PFC temperature sensor error
of fan 1
72
Charging circuit-EF1 Charging circuit error of fan 1
73
DC under-voltageF2
DC busbar under-voltage or voltage drop error of
fan 2
74
DC over-voltageF2
DC busbar over-voltage or voltage drop error of
fan 2
75 IPM errorF2 IPM failure of fan 2
76
Startup failureF2 Startup failure of fan 2
77
Dri-Mod resettingF2 Drive module resetting of fan 2
78 Fan-Over-currentF2 Over-current of fan 2
79 Current circuit SEF2
Current sensing circuit error or current sensor
error of fan 2
80
DesynchronizingF2 Desynchronizing of fan 1
A Series Modular-type Air-cooled (Heat Pump) Chiller