It is equipped with the top-end microcomputer control system which is capable of providing
well-rounded protection and self-diagnosis.
High reliability
It is constructed of well-designed refrigeration parts and well-designed system, structure
and electric control, adequately guaranteeing reliable operation
Remote ON/OFF
The unit can be started or stopped by the ON/OFF key operation.
Equilibrium running
It indicates each compressor will run alternately so as to extend their service life.
Shiftwork of water pumps
Two water pumps can work alternately with equilibrium runtime so as to extend their service
life and lower the maintenance difficulty.
3.1.4 Nominal Operating Conditions
Item
Water side Air side
Water flow m3/
h·kW
Outlet
temparature
(℃)
Dry bulb
temperature
(℃)
Wet bulb
temperature
(℃)
Cooling
0.172
7 35
Heat pump
45 7 6
3.1.5 Operation Range
Please run the unit under the specified operation range as shown in the table below:
R410A Series
Item
Water Side Air Side
Leaving Water
Temperature(℃)
Water Temperature
Difference(℃)
Ambient DB
Temperature(℃)
Cooling
520 2.56 –1552
Heating
3550 2.56 -2040
maximum and minimum entering water pressures:
Item
Minimum entering water
pressures
Maximum entering water
pressures
Cooling
0.06MPa 1.6MPa
Heating
3.2 Unit Performance Curves
Here are curves indicating the unit performances in cooling and heating states.
A Series Modular-type Air-cooled (Heat Pump) Chiller

Table of Contents

Other manuals for Gree A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree A Series and is the answer not in the manual?

Gree A Series Specifications

General IconGeneral
BrandGree
ModelA Series
CategoryChiller
LanguageEnglish