5.6.3 Specification of Power Cord and Air Switch
See the table below for selection of the power lines and the air switches.
Model
Power Supply
Min. sectional area of the
power cable(mm
2
)
Capability of the
Air Switch Live
(A)
Live
Line
Neutral
Line
Earth
Line
LSQWRF35VM/
NaA-M
380V~415VAC 3Ph
50Hz
6 6 6 32
LSQWRF60VM/
NaA-M
380V~415VAC 3Ph
50Hz
16 16 16 63
LSQWRF65VM/
NaA-M
380V~415VAC 3Ph
50Hz
16 16 16 63
Notes:
(1)The specifications of the breaker and power cable listed in the table above are
determined based on the maximum power (maximum amps) of the unit.
(2)The specifications of the power cable listed in the table above are applied to the conduit-
guarded multi-wire copper cable (like, JYV copper cable, consisting of PV insulated wires
and a PVC cable jacket) used at 45℃ and resistible to 90℃(GB/T 16895.15-2002). If the
working condition changes, they should be modified according to the related national
standard.
(3)The specifications of the breaker listed in the table above are applied to the breaker with
the working temperature at 40℃. If the working condition changes, they should be
modified according to the related national standard.
5.6.4 Wiring of the Electric Control Cabinet
■ LSQWRF35VM/NaA-M,LSQWRF60VM/NaA-M, LSQWRF65VM/NaA-M