5.6.5 Filed Wiring
Safety Codes
(1)All wiring shall comply with applicable codes and engineering requirements.
(2)All field wiring shall be performed by the qualified electrician.
(3)Never perform wiring before the power supply is cut off.
(4)Any damage caused by the improper external wiring shall be at the installer’s expense.
WARNING
Only copper conductor is allowed.
How to wire the power lines to the electric box
(1)The power cord must be routed inside the conduit.
(2)The power cord must enter the electric box through a rubber or plastic ring to avoid any
damaged caused by the sharp edge of the metal sheet.
(3)The power cord close to the electric box must be attached securely to prevent the termi-
nal block of the electric box affected by the outside force. The Power cord shall be installed
A Series Modular-type Air-cooled (Heat Pump) Chiller