62
Water (t≤95) lines
Welded steel, seamless steel, galvanized steel, nodular
cast iron, composited aluminum and plastic (PAP1,
XPAP2, RPAP5), PB, PE-X
Water (t≤60) lines
Welded steel, seamless steel, galvanized steel, PP-R,
composited aluminum and plastic (PAP1, XPAP2,
RPAP5), PB, PE-X, PE-RT
Cooling wter lines
Welded steel, seamless steel, galvanized steel, nodular
cast iron
Drain lines
PVC,UPVC
Condensation lines
Galvanized steel, PE, PVC, UPVC
5.2.3.2 Insulation
Typically the refrigerant copper tubes, air ducts, chilled water tubes and condensation tubes
should be thermally insulated by the commonly used plastic insulation rather than glass wool,
PE or PEF.
Diameter(mm)
Gas-expanded Rubber
Glass Wool
DN15DN25 15mm 20mm 30mm 30mm
DN32DN50 25mm 30mm 35mm 35mm
DN65DN80 30mm 35mm 35mm 40mm
≥DN100 35mm 40mm 40mm 45mm
Note: under the tropical climate, the insulation should be thickened or doubled.