74
6 of total rated flow rate per hour of each module (for instance, for some project with four
modularized LSQWRF60VM/Na-M units, if the rated water flow of each unit is 10.3m
3
/h,
then the required capacity of the whole project should be larger than 10.3*4*1/6=6.87m
3
/
h). When the water course is quite short, a water tank is required; otherwise the service life
of the unit would be affected.
NOTE
Never use salt mixture to prevent the unit from being corroded.
How to install the water system
A Series Modular-type Air-cooled (Heat Pump) Chiller