GREE DC INVERTER HEAT PUMP CONDENSING UNIT
89
Disassembly of compressor
NOTE:Before removing the compressor, make sure there is no refrigerant in the pipeline and power is cut off.
Step
Picture
Work instruction
4. Remove the compressor
from the chassis.
Take out the compressor
and replace it.
NOTE:When replacing the
compressor, avoid touching
the nearby pipeline and
components.
5. Fix the new compressor back
onto the chassis.
After replacing the
compressor, tighten up the
screws at the foot of
compressor.
6. Connect the compressor
suction port and exhause
port with the pipes.
Weld the compressor
connection pipes and
connect them to the
compressor.
NOTE: When replacing the
compressor, avoid touching
the nearby pipeline and
components.

Other manuals for Gree FLEXX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree FLEXX Series and is the answer not in the manual?

Gree FLEXX Series Specifications

General IconGeneral
TypeHeat Pump
SeriesFLEXX
SEERUp to 20
HSPFUp to 10
RefrigerantR410A
Heating Operation Range-22°F to 75°F
Cooling Operation Range5°F to 122°F
Operating Temperature Range (Heating)-22°F to 75°F
Operating Temperature Range (Cooling)5°F to 122°F
Energy Efficiency Ratio (EER)Up to 12.5
Dimensions (Outdoor Unit)Varies by model
Weight (Outdoor Unit)Varies by model
Compressor TypeInverter
Power Supply208/230V, 1Ph, 60Hz
Noise LevelAs low as 55 dB(A)

Related product manuals