3.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between
inverter and AC input power source. This will ensure the inverter can be securely disconnected during
maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is
20A for 2KVA, 32A for 3KVA, 40A for 4KVA and 50A for 5KVA.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do not mis-connect input
and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to use appropriate cable for AC input
connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model Series (230V)
Gauge
Torque Value
SPF 2000TL
14 AWG
0.8~ 1.0 Nm
SPF 3000TL
12 AWG
1.2~ 1.6 Nm
SPF 4000TL
10 AWG
1.4~ 1.6Nm
SPF 5000TL
8 AWG
1.4~ 1.6Nm
Please follow below steps to implement AC input/output connection:
1.
Before making AC input/output connection, be sure to open DC protector or disconnector first.
2.
Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
3.
Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be
sure to connect PE protective conductor first.
Ground (yellow-green)
LLINE (brown or black)
NNeutral (blue)
WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
4.
Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be
sure to connect PE protective conductor first.
Ground (yellow-green)
LLINE (brown or black)
NNeutral (blue)
5.
Make sure the wires are securely connected.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause
utility short-circuited when these inverters are worked in parallel operation.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPF 5000TL HVM and is the answer not in the manual?

Growatt SPF 5000TL HVM Specifications

General IconGeneral
Rated Power5000W
Input Voltage230VAC
Output Voltage230VAC
Frequency50/60Hz
Efficiency93%
Battery Voltage48V
Max. PV Array Power6000W
Max. DC Voltage450VDC
Number of MPPT Trackers1
Max. Input Current18A
Max. AC Output Current21.7A
Max. Charging Current80A
Max. Discharging Current80A
Operating Temperature Range-10°C to 50°C
Protection DegreeIP20
Cooling MethodFan
Dimensions330 x 485 x 135 mm
CommunicationRS232, USB
MPPT Range120-430VDC