discharging
power
Type of Battery lithium
/Lead-acid
lithium
/Lead-acid
lithium
/Lead-acid
lithium
/Lead-acid
lithium
/Lead-acid
lithium
/Lead-acid
Efficiency
Max. efficiency
97.2% 97.2% 97.3% 97.4% 97.5% 97.6%
Euro weighted
efficiency
97% 97% 97.1% 97.1% 97.2% 97.2%
MPPT efficiency
99.5% 99.5% 99.5% 99.5% 99.5% 99.5%
Protection devices
Safety level Class Il
Overvoltage
category
PV:II AC:III Others:I
Ingress
protection
IP65
Inverter topology
Non-isolated
Operating
temperature
range
–25°C ... +60°C (-13...+140) with derating above 45°C /113
Safety level Class I
Ingress
protection
IP65
DC switch Integrated
DC
reverse-polarity
protection
Integrated
DC Surge
protection
Type II
Insulation
resistance
monitoring
Integrated
AC surge
protection
Type II
AC short-circuit
protection
Integrated
Ground fault
monitoring
Integrated
Grid monitoring
Integrated
Anti-islanding
protection
Integrated(Active Frequency Drift)
Residual-current
monitoring unit
Integrated
General Data

Other manuals for Growatt SPH5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPH5000 and is the answer not in the manual?

Growatt SPH5000 Specifications

General IconGeneral
ModelSPH5000
TypeHybrid Inverter
Rated Power5000 W
Max. DC Voltage550 V
Max. Output Current22 A
Weight25 kg
Max. DC Power6000 W
Start Voltage150 V
Nominal DC Voltage360 V
Number of MPP Trackers2
AC Nominal Power5000 W
Max. AC Apparent Power5000 VA
AC Nominal Voltage230 V
AC Voltage Range180-280V
Nominal Grid Frequency50/60Hz
Total Harmonic Distortion (THDi)<3%
Power Factor Adjustment Range0.8 leading to 0.8 lagging
DC Injection Current<0.5% In
Switching Time<10 ms
Max. Charge/Discharge Power5000 W
Max. Charge/Discharge Current100 A
Protection degreeIP65
Max. PV Input Voltage550 V
Cooling MethodNatural Convection
Communication with BMSCAN
Operating Temperature Range-25°C to 60°C
MPPT Voltage Range120 V - 550 V