19
7.6.2 Operating mode
This display shows the actual operating mode (Stop,
Min., Normal or Max.) and where is was selected
(Pump, R100, BUS or External).
7.6.3 Head and flow
The actual head and flow of the pump.
If "<" is indicated in front of the flow, the flow is less
than the displayed value.
7.6.4 Speed
The actual pump speed.
7.6.5 Liquid temperature
The actual temperature of the pumped liquid.
7.6.6 Power input and power consumption
Actual power input and power consumption of the
pump.
The value of power consumption is an accumulated
value and cannot be set to zero.
7.6.7 Operating hours
Operating hours of the pump.
The value of operating hours is an accumulated
value and cannot be set to zero.
7.7 Menu INSTALLATION
This menu shows the settings that should be consid-
ered when installing the pump.
7.7.1 Control mode
Description of function, see section 6.1 Control
modes or 6.4 Constant-curve duty.
Select one of the control modes:
•AUTO
ADAPT
• Prop. pressure (proportional pressure)
• Const. pressure (constant pressure)
• Const. curve (constant curve).
Setting of setpoint and curve is carried out in display
7.5.1 Setpoint in menu OPERATION (not possible
when the pump is in AUTO
ADAPT mode).
7.7.2 Automatic night-time duty
In this display, automatic night-time duty can be acti-
vated or deactivated.
Automatic night-time duty can be set to:
• Active
• Not active,
irrespective of the control mode selected.