Grundfos PHT A N - Operating Screens and Menu Navigation

Grundfos PHT A N
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.grundfos.co.uk
GRUNDFOS INSTRUCTIONS
14
7.2 Start-Up Sequence.
Upon powering up the unit, the controller will display the PHT * and Grundfos for 3 seconds
followed by the software version for a further 3 seconds.
PHT *
Grundfos
14.25
7.3 Main Operating Screen.
When the unit is operating normally and the status is healthy the display will include:
Status: OK / System 1 Pressure and Value / Current Date and Current Time:
Status: OK
System 1 Pressure 1.5 Bar
23/08/2017
14.25
With the PHT A-T configuration, the display will also show System 2 Pressure and value:
Status: OK
System 1 Pressure 1.5 Bar
System 2 Pressure 2.0 Bar
23/08/2017
14.25
If a fault condition is active, then the Status will show FAULT and the line below will carry a
message indicating the fault. If more than one fault exists then the first detected fault is shown
until cleared, the next fault is then displayed.
Status: FAULT
Low Water
System 1 Pressure 1.5 Bar
23/08/2017
3/08/2017
Software Version
V*.*
To interrogate all existing fault
conditions press the DOWN key and
scroll through the active faults.
See section 7.7 for more details.
NOTE