ANALOG CONTROL
117
EXT-V/R CC
CONT
21
This line uses an external voltage or resistance to
control the output current.
External voltage control (F-91: 1); External resistor
control (F-91: 2, F-91: 3).
0 to 5V or 0 to 5k; 0 % to 100 % of the rated
output current (F-97: 0).
0 to 10V or 0 to 10k; 0 % to 100 % of the rated
output current (F-97: 1).
EXT-V/R CV
CONT
22
This line uses an external voltage or resistance to
control the output voltage.
External voltage control (F-90: 1); External resistor
control (F-90: 2, F-90: 3).
0 to 5V or 0 to 5k; 0 % to 100 % of the rated
output voltage (F-97: 0).
0 to 10V or 0 to 10k; 0 % to 100 % of the rated
output voltage (F-97: 1).
A COM
23
This the common line for the external signal pins 7
to 10, 12, 13, 19, 21, 24, and 25. It is connected
internally to the negative output.
I MON
24
Output current monitor.
0 % to 100 % of the rated output current is
generated as a voltage between 0V and 5V (F-96: 0)
or a voltage between 0V and 10V (F-96: 1).
V MON
25
Output voltage monitor.
0 % to 100 % of the rated output voltage is
generated as a voltage between 0V and 5V (F-96: 0)
or a voltage between 0V and 10V (F-96: 1).
1. Open collector output: 30V max, 8mA max.
The common line for the status pins is floating (isolated voltage of
60 V or less). It is isolated from the control circuit.