ANALOG CONTROL 
133 
Remote Monitoring 
The PSU power supplies have remote monitoring support for 
current and voltage output. They also support monitoring of 
operation and alarm status.  
 
  External monitoring of output voltage and current  → from page 
133 
  External monitoring of operation mode and alarm status → from 
page 136 
  External Trigger In/Out → from page 139 
External Voltage and Current Monitoring 
 
The analog connector is used to monitor the 
current (IMON) or voltage (VMON) output.  
An output of 0~10V or 0~5V (depending on the 
configuration) represents the voltage or current 
output of 0~ rated current/voltage output. 
  IMON = (current output/full scale) × 10 or 
5. 
  VMON = (voltage output/full scale) × 10 or 
5. 
The PSU doesn’t need to be configured to use 
external voltage or current monitoring, 
however the voltage or current output range 
does need to be configured. The monitor output 
voltage can be configured as either 0~10V or 
0~5V.