Programmable Temperature & Humidity Controller
30
●
Step/Hold
It is enabled only during program operation. Enter a key or set Hold/Step in [System menu] –
[DI configuration] – [Configuration type] and then set external contact input2(DI2) to ON in order for
Hold or external contact input3(DI3) to ON for Step.
▶ DI state screen
Parameter Description
Stop the operation of current segment and continue with next segment operation.
Run Step in Wait or Hold state to cancel it and continue with next segment.
During operation, press Hold button to maintain the momentary setting value
for unlimited control regardless of the setting time.
Press Hold button again to cancel it and run the program.
①
②
③
④
No. Description
1
Displays selected DI image. The image can be copied in [System] – [Main menu] - [System menu].
Image is sized to 310 X 210.
2
Displays selected DI name. It can be set in [System] – [Main menu] - [System menu].
3
Turns off buzzer for DI.
4
Select DI. If DI is colored in red, DI contact is ON.
Fig. 45) DI state screen
step
HOLD