Fluid fill:
Piping has been flushed with external water until water runs clear.
100psi gas has been applied to piping loop for 30 minutes to check for leaks.
Glycol concentrate, provided with the OPC, has been diluted with drinking/spring water to
achieve a 35-40% glycol/drinking water solution.
Tank and entire piping loop have been filled with 35-40% glycol/drinking water solution,
and piping loop has been purged of air.
Additional propylene glycol/drinking water solution is on-hand for service contractor to top
off system when start-up is performed.
Piping has been checked for fluid leaks.
Installation Completed By (Please Print):
Company: ________________________________ Phone: _______________ Email: _______________
Name: ____________________________________________________ Title: _________________________
Signature: ________________________ Date: ________________