Installation, use and maintenance manual rev00
43 - 48
Now we see in detail the different screen of the installer menu:
On the left you see the screen 1 of installer menu, which allows to modify the fan speed in the
functioning phases:
1. Recirculation: OFF, MIN, MEDIUM or MAX
2. Dehumidification: MEDIUM or MAX
3. Heating: (if present): MEDIUM or MAX, connected to the speed in dehumidification
It is recommended not to set the recirculation speed on OFF, because each time the unit goes
in stand-by, it turns off the ventilation and the chlorine present in the swimming pool could
damage the components of the unit .
The screen 2 of the installer menu allows to modify the timer which signals the filter cleaning.
On the left you see the screen 3 of the installer menu, which allows to modify the differentials
that manage the request for dehumidification.
On the left you see screen 4 of the installer menu, which allows to modify the differentials that
manage the request for heating.
This screen is present only if the option hot water coil with valve or electrical heaters has been
chosen.
On the left you see the screen 5 of the installer menu, which allows the activation of the contact
for the on/off at distance and, if necessary, it inverts the functioning logic.
This screen is present only if the modbus communication is not active.
Without inverting the logic:
- contact open unit off
- contact closed unit on
On the left you see the screen 6 of the installer menu, which allows to activate the contact on/off
for dehumidification and, if necessary, to invert the functioning logic.
This screen is present only if the modbus communication is not active
Without inverting the logic:
- contact open request for dehumidification non-active
- contact closed request for dehumidifcation active