3 Product Description  F30 01 
Page 12 of 52  HI 800 145 E Rev. 2.00 
3.1.1.1  Reaction in the Event of a Fault 
If the device detects a fault on a digital input, the user program processes a low level in 
accordance with the de-energized to trip principle. 
The device activates the FAULT LED. 
In addition to the channel signal value, the user program must also consider the corresponding 
error code.  
The error code allows the user to configure additional fault reactions in the user program. 
 
3.1.1.2  Line Control 
Line control is used to detect short-circuits or open-circuits and can be configured for the F30 
system, e.g., on EMERGENCY STOP inputs complying with Cat. 4 and PL e in accordance with 
EN ISO 13849-1. 
To this end, connect the digital outputs DO 1 through DO 8 of the system to the digital inputs DI 
of the same system as follows: 
 
  EMERGENCY STOP 1 
  EMERGENCY STOP 2 
  EMERGENCY STOP switches in 
accordance with EN 60947-5-1 and 
EN 60947-5-5 
Figure 2:  Line Control 
The controller pulses the digital outputs to detect short-circuits and open-circuits on the lines 
connected to the digital inputs. To do so, configure the Value [BOOL] -> system variable in 
SILworX or the DO[0x].Value system signal in ELOP II Factory. The variables for the pulsed 
outputs must begin with channel 1 and reside in direct sequence, one after the other. 
If the following faults occur, the FAULT LED located on the front plate of the controller blinks, 
the inputs are set to low level and an (evaluable) error code is created: 
  Cross-circuit between two parallel wires. 
  Invalid connections of two lines (e.g., DO 2 to DI 3), 
  Earth fault on one wire (with earthed ground only). 
  Open-circuit or open contacts, i.e., including when one of the two EMERGENCY STOP 
switches mentioned above has been engaged, the FAULT LED blinks and the error code is 
created.