4 Start-up
To start up the controller, it must be mounted, connected and configured in the programming
tool.
4.1 Installation and Mounting
The controller is mounted on a 35 mm DIN rail such as described in the system manual for
compact systems.
When laying cables (long cables, in particular), take appropriate measures to avoid interference,
e.g., by separating the signal lines from the power lines.
When dimensioning the cables, ensure that their electrical properties have no negative impact
on the measuring circuit.
4.1.1 Connecting the Digital Inputs
Use the following terminals to connect the digital inputs:
Terminal Designation Function
13 LS+ Sensor supply of the inputs 1...4
14 1 Digital input 1
15 2 Digital input 2
16 3 Digital input 3
17 4 Digital input 4
18 L- Ground
Terminal Designation Function
19 LS+ Sensor supply of the inputs 5...8
20 5 Digital input 5
21 6 Digital input 6
22 7 Digital input 7
23 8 Digital input 8
24 L- Ground
Terminal Designation Function
25 LS+ Sensor supply of the inputs 9...12
26 9 Digital input 9
27 10 Digital input 10
28 11 Digital input 11
29 12 Digital input 12
30 L- Ground
Terminal Designation Function
31 LS+ Sensor supply of the inputs 13...16
32 13 Digital input 13
33 14 Digital input 14
34 15 Digital input 15
35 16 Digital input 16
36 L- Ground