3 Product Description F30 01
Page 26 of 52 HI 800 145 E Rev. 2.00
Digital outputs
Number of outputs 8 (non-galvanically separated)
Output voltage ≥ L+ minus 2 V
Output current Channels 1...3 and 5...7: 0.5 A up to 60 °C
The output current of the channels 4 and 8 depends on the
ambient temperature.
Ambient temperature Output current
< 50 °C 2 A
50…60 °C 1 A
Minimum load 2 mA for each channel
Internal voltage drop max. 2 V at 2 A
Leakage current (with low level) max. 1 mA at 2 V
Behavior upon overload
The affected output is switched off and cyclically switched on
again
Total output current max. 7 A
Upon overload, all outputs are switched off and cyclically
switched on again
Table 17: Specifications for the Digital Outputs
3.5.1 Product Data F30 011 (-20 °C)
The F30 011 (-20 °C) model variant is intended for use at the extended temperature range of
-20…+60 °C. The electronic components are coated with a protective lacquer.
F30 011
Operating temperature -20…+60 °C
Weight approx. 1.2 kg
Table 18: Product Data F30 011 (-20 °C)
3.5.2 Product Data F30 014
The F30 014 model variant is intended for use in railway applications. The electronic
components are coated with a protective lacquer.
F30 014
Operating temperature -25…+70 °C (temperature class T1)
Output current Channels 1...3 and 5...7: 0.5 A
The output current of the channels 4 and 8 depends on the
ambient temperature.
Ambient temperature Output current
< 50 °C 2 A
50…60 °C 1 A
> 60 °C 0.5 A
Weight approx. 1.2 kg
Table 19: Product Data F30 014
The controller F30 014 meets the conditions for vibrations and shock test according to
EN 61373, category 1, class B.