HIMA HIMatrix F30 011 - Product Data F30 011 (-20 °C); Product Data F30 014; Table 17: Specifications for the Digital Outputs; Table 18: Product Data F30 011 (-20 °C)

HIMA HIMatrix F30 011
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Product Description F30 01
Page 26 of 52 HI 800 145 E Rev. 2.00
Digital outputs
Number of outputs 8 (non-galvanically separated)
Output voltage L+ minus 2 V
Output current Channels 1...3 and 5...7: 0.5 A up to 60 °C
The output current of the channels 4 and 8 depends on the
ambient temperature.
Ambient temperature Output current
< 50 °C 2 A
50…60 °C 1 A
Minimum load 2 mA for each channel
Internal voltage drop max. 2 V at 2 A
Leakage current (with low level) max. 1 mA at 2 V
Behavior upon overload
The affected output is switched off and cyclically switched on
again
Total output current max. 7 A
Upon overload, all outputs are switched off and cyclically
switched on again
Table 17: Specifications for the Digital Outputs
3.5.1 Product Data F30 011 (-20 °C)
The F30 011 (-20 °C) model variant is intended for use at the extended temperature range of
-20…+60 °C. The electronic components are coated with a protective lacquer.
F30 011
Operating temperature -20…+60 °C
Weight approx. 1.2 kg
Table 18: Product Data F30 011 (-20 °C)
3.5.2 Product Data F30 014
The F30 014 model variant is intended for use in railway applications. The electronic
components are coated with a protective lacquer.
F30 014
Operating temperature -25…+70 °C (temperature class T1)
Output current Channels 1...3 and 5...7: 0.5 A
The output current of the channels 4 and 8 depends on the
ambient temperature.
Ambient temperature Output current
< 50 °C 2 A
50…60 °C 1 A
> 60 °C 0.5 A
Weight approx. 1.2 kg
Table 19: Product Data F30 014
The controller F30 014 meets the conditions for vibrations and shock test according to
EN 61373, category 1, class B.