E-Compact Medium Power
ALARM
ALARM DESCRIPTION
PSU __ Critical Low AC Line Voltage
AC Voltage at PSU is less than 170Vac
Default system action: Shutdown
PSU __ Critical High Current
Power at PSU indicate exceeds 1300Watts
Default system action: Shutdown
PSU __ High Temperature
Temperature at PSU is greater than 60°C (140ºF).
Default system action: Notification
PSU __ Critical High Temperature
Temperature at PSU is greater than 63°C (145.4ºF).
Default system action: Shutdown
PSU __ High Current
Current at PSU is greater than 24A.
Default system action: Notification
PSU __ Low Voltage
DC Output Voltage at PSU is less than 3V of the programmed.
Default system action: Shutdown
PSU __ High Voltage
DC Output Voltage at PSU is greater than 3V of the
programmed.
Default system action: Shutdown
PSU __ Low AC Line Voltage
AC Voltage at PSU is less than 180Vac
Default system action: Notification
PSU __ Shutdown
The PSU is Shutdown.
FAN __ Warning
Fan rotation reaches ±1000RPM in relation to software
programmed value.
Default system action: Notification
FAN __ Failure
Fan rotation reaches ±2000RPM in relation to software
programmed value.
Default system action: Notification