Part Optional function
Indivi
dual
settin
g
Settings
Condition
setting
Description
E4
Pre-cooling / pre-heating
period
O
KPI:
This function delays start-up of the
ventilation unit with energy / heat recovery
00 Standard
01 30 minutes
02 60 minutes
Econofresh kit
00 Standard
02 CO
2
sensor
E5
Not used O
00 Not used
–
01
Used as setting
for conditions
00
E6
Fan operating time after
stoppage of the indoor unit
in cooling mode
O
00 Not available
This prevents condensation from
accumulating in the unit by keeping the fan
running after it is switched off.
01 60 minutes
02 120 minutes
E7
Not used O
00 Not used
–
01
Used as setting
for conditions
00
E8
Fan operating control after
stoppage of the indoor unit
in heating mode
O
00 Not available
This function reduces the unit fan speed to
prevent cold draughts.
01 Available
E9
Not used O
00 Not used
–
01
Used as setting
for conditions
00
EA
Not used O
00 Not used
–
01
Used as setting
for conditions
00
Eb
Fan operating control after
stoppage of the indoor unit
in cooling mode
O
00 Not available
This function reduces the unit fan speed to
reduce the spreading of smells and
humidity.
01 Low
02 Slow
EC
Forced stoppage in cooling
mode
O
00 Not available
This function is used to force stoppage
when cooling is complete.
01 Available
Ed
Not used O
00 Not used
–
01
Used as setting
for conditions
00
EE
Automatic fan speed
control
O
00 Not available This function limits the operating of the unit
by automatically controlling the fan speed
when the room temperature is close to the
set temperature.
01 Available
6 Optional functions
202
SMGB0063 rev. 1 - 10/2010