Fit the false ceiling panels along the unit.
Continue for all installation types
Check that the condensate discharge system in the indoor unit
works correctly. To do so, check the level of the drain pan using a
spirit level or a clear flexible pipe full of water. The rear of the unit
where the drain hose is located must be around 3 mm lower than
the front side.
Secure the drain hose with the clamp and adhesive supplied.
2 Unit installation
41
SMGB0063 rev. 1 - 10/2010