EasyManua.ls Logo

Hitachi SJ300 Series

Hitachi SJ300 Series
47 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
43
TORQUE CHARACTERISTICS
Typical torque performance based on
V/f pattern (below) is shown to the right.
High starting torque is accomplished even with a general-purpose motor by the torque calculation software
that Hitachi has uniquely developed first in the industry.
DERATING DATA
The SJ300 series can be used at ambient temperature of
-
10˚C to 50˚C.
However, when using at 50˚C, derating is required.
High starting torque of 200% or greater at 0.5Hz
Continuous operating torque of 100% within 1:10 speed range. (Up to 3.7kW)
150
175
200
130
125
100
95
90
80
75
50
45
25
0
0.5 6 10 20 30 40 50 60 70 80 90 100 110 120
525 50 75 100
(continuous torque)
Continuous operating torque of V/f control
Continuous operating torque of
sensorless vector control
Frequency(Hz)
Output torque(%)
Example of SJ300-015LFU driving a Hitachi's
1.5kw 4-pole totally enclosed type motor (Base frequency of 60 Hz)
(Note: Torque characteristics may vary according to the model.)
V
Hzf
V/f pattern
100(%)
1  
-
 50
1  
-
 60
100
120
Short time period operating
torque of V/f control
Short time period operating
torque of sensorless vector control
Derating data for ambient temperature 50˚C, input voltage 240/480V.
15
20
60
70
80
90
100
468101214
450HF
007
-
185HF
370HF
300HF
220HF
1100HF
900HF
750HF
550HF
1320, 1500HF
Carrier frequency (kHz) Carrier frequency (kHz)
20
60
70
80
90
100
468101214
004
-
110LF
150LF
370LF
185LF
300LF
550LF
220LF
450LF
(
200V class
)(
400V class
)
Output current
(
Ratio to the rating : %
)
Output current
(
Ratio to the rating : %
)