Appendix E: Power distribution units for Hitachi
Universal V2 Rack
The Hitachi Universal V2 Rack is equipped with specic power distribution units (PDU) for
Americas, APAC, and EMEA regions. The PDUs can provide electrical power to the storage
system in a single-phase or three-phase conguration.
Caution:
■
Before installing third-party devices into the rack, check the electrical
current draw of each device. Verify the electrical specications and
allowable current load on each PDU before plugging the device into the
PDU.
■
Balance the electrical current load between available PDUs.
Americas single-phase PDU 1P30A-8C13-3C19UL.P
The following gure and table describes the specications of the PDU.
Figure 1 Americas PDU for the Hitachi Universal V2 Rack (Single-phase PDU
1P30A-8C13-3C19UL.P)
Part Number Region Phase Description
1P30A-8C13-3C19U
L.P
Americas Single
■
208V, 30A (24A
rated) 60Hz
■
8 IEC C13 + 3 IEC
C19 sockets
■
NEMA L6-30P
input power plug
■
4.5 m (14.76
feet) cable
Appendix E: Power distribution units for Hitachi Universal V2 Rack
Hitachi Virtual Storage Platform F700 Hardware Reference Guide 86