48 PMML0291A rev.2 - 09/2014
DHW TANK OPERATION
8 DHW TANK OPERATION
Operation switches location
The LCD Controller (PC-S80TE) is integrated into the DHW tank.
User interface service cover
To protect the LCD controller and the manometer.
Manometer
Manometer to control water outlet pressure in the installation.
LCD Controller
Unit interface that helps user to congure all available settings.
The LCD controller working mode is very simple, with 7 buttons that make possible the access to all the display menus, which can be
shown by the LCD liquid crystal display.
Run/Stop
Pressing this button, it will be switched RUN/STOP the selected zone, or all the unit
if there is no zone selected.
Arrow buttons
Helps user to move through the menus and views.
Ok button
Select variables due to be edited and conrm the selected value.
Back button
Used as a cancel button when editing an item or for going back to the main menu
from the global view.
Liquid crystal display
Screen where controller software is displayed.
HITACHI
OK
Thermostat (manual reset) Units DHW tank
Cut-Out contactors ºC 85
Current A 16 (AC1)
Voltage V 230V
Coil Voltage V 207~253V
Heating resistances Units DHW tank
Power input kW 2.0
Voltage V 230V
Diameter mm 8.5
Resistances whole xing are nut “G 1 1/4 (brass)
Specic heat load W/cm
²
13.8
Material - Incoloy 825
Resistance cord - Ni-Cr 80/20 Ø 0.45mm
Sensor - NTC 20k
9 CONTROL DEVICE SETTING