Configuration
24 UDC3300 Basic Model: DC33XB User Manual 12/00
3.4 SP Ramp, SP Rate, or SP Programming Set Up Group
Table 3-3 SP Ramp Function Prompts
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
If SP Rate and SP Programming are disabled
SP RAMP
Single Setpoint Ramp
Selection
DISABL
ENABLE
DISABL
TIME MIN
Single Setpoint Ramp
Time (SP Ramp enabled)
0 to 255 minutes 3
FINAL SP
Sinlge Setpoint Final
Setpoint (SP Ramp
enabled)
Enter a value within the setpoint
limits.
1000
If SP Ramp and SP Programming are disabled
SP RATE
Setpoint Rate DISABL
ENABLE
DISABL
EU/HR UP
Rate Up Value for
Loop 1 (SP Rate enabled)
0 to 9999
in engineering units per hour
0
EU/HR DN
Rate Down Value for
Loop 1 (SP Rate enabled)
0 to 9999
in engineering units per hour
0
If SP Ramp and SP Rate are disabled
SP PROG*
*requires SP
Program option
Setpoint Ramp/Soak
Programming
DISABL
ENABLE
SP PROG must be enabled to
view the remaining prompts.
DISABL
STRT SEG
Start Segment Number 1 to 11
(odd segment number only)
––
END SEG
End Segment Number 2 to 12
Always end in a soak segment
(2, 4, ... 12)
––
RAMPUNIT
Engineering Units for
Ramp Segments
TIME (hours.minutes)
EU/MIN(engineering
units/minute)
EU/HR(engineering units/hour)
TIME
RECYCLES
Number of Program
Recycles
0 to 99 recycles ––