3.10 Loop 1 Control Parameters Set Up Group
Table 3-9 Control Group Function Prompts
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
PV SOURC
Process Variable Source INP 1 IN AL1
INP 2
INP 1
PID SETS
Tuning Parameter Sets 1 ONLY
2KEYBD
2PV SW
2SP SW
1 ONLY
SW VALUE
Automatic Switchover
Value
Value in engineering units within
PV or SP range limits
0.00
LSPS
Local Setpoint Source 1 ONLY
TWO
THREE (Selection automatically
disables RSP SRC)
1 ONLY
RSP SRC
Remote Setpoint Source NONE IN AL1
INP 2
NONE
AUTOBIAS
Automatic Bias ENABLE
DISABL
DISABL
SP TRACK
Local Setpoint Tracking NONE
PV
RSP
NONE
PWR MODE
Power Up Mode Recall MANUAL
A LSP
A RSP
AM SP
AM LSP
MANUAL
PWR OUT
TPSC Output Start-up
Mode
LAST
FSAFE
LAST
SP HiLIM
Setpoint High Limit 0 to 100% of span input in
engineering units
1000
SP LoLIM
Setpoint Low Limit 0 to 100% of span input in
engineering units
0
ACTION
Control Output Direction DIRECT
REVRSE
REVRSE
OUT RATE
Output Change Rate ENABLE
DISABL
Does not apply to 3 Position Step
Control algorithm.
DISABL
PCT/M UP
Output Rate Up Value 0 to 9999% per minute 0