Configuration
32 UDC3300 Basic Model: DC33XB User Manual 12/00
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
PCT/M DN
Output Rate Down Value 0 to 9999% per minute 0
OUTHiLIM
High Output Limit –5.0 to 105% of output 100
OUTLoLIM
Low Output Limit –5.0 to 105% of output 0.0
I Hi LIM
High Reset Limit Within the range of output limits 100.0
I Lo LIM
Low Reset Limit Within the range of output limits 0.0
DROPOFF
Controller Dropoff Value –5 to 105% of output 0
DEADBAND
Output Relay Deadband Time Duplex:
–5.0 to 25.0%
On/Off Duplex:
0.0 to 25.0%
Position Prop. and 3P Step:
0.5 to 5.0%
1.0
OUT HYST
Output Relay Hysteresis 0.0 to 100.0% of PV Span for
On/Off control.
0.5
FAILMODE
Failsafe Mode NO LAT
LATCH
NO LAT
FAILSAFE
Failsafe Output Value for
all outputs except 3P Step
Set within the range of the
output limits. 0 to 100%
0.0
Failsafe Output Value for
3P Step
0 PCT (motor goes to closed
position)
100PCT (motor goes to open
position)
- -
SW FAIL
PDMR/ Position
Proportional Motor Position
when Slidewire Fails
0 PCT (motor goes to closed
position)
100PCT (motor goes to open
position)
- -
MAN OUT
Power-up Preset Output
for Manual Output
Within the range of output limits - -
AUTO OUT
Power-up Preset Output
for Automatic Output
Within the range of output limits - -
PBorGAIN
Proportional Band or Gain
Units
PB PCT
GAIN
GAIN
MINorRPM
Reset Units RPM
MIN
MIN