Environmental and Operating Conditions
12/00 UDC3300 Basic Model: DC33XB User Manual 63
6. Appendix A Environmental and Operating Conditions
Parameter Reference Rated Operative
Limits
Transportation and
Storage
Ambient
Temperature
25 °C ± 3 °C
77 °F ± 5 °F
15 °C to 55 °C
58 °F to 131 °F
0 °C to 55 °C
32 °F to 131 °F
40 °C to 66 °C
40 °F to 151 °F
Relative Humidity
10 to 55* 10 to 90* 5 to 90* 5 to 95*
Vibration
Frequency (Hz)
Acceleration (g)
0
0
0 to 70
0.4
0 to 200
0.6
0 to 200
0.5
Mechanical Shock
Acceleration (g)
Duration (ms)
0
0
1
30
5
30
20
30
Voltage (Vdc)
+24 ± 1 20 to 27 20 to 27 - -
Voltage (Vac)
90 to 240 Vac
24 Vac
120 ± 1
240 ± 2
24 ± 1
90 to 240
20 to 27
90 to 264
20 to 27
- -
- -
- -
Frequency (Hz)
(For Vac)
50 ± 0.2
60 ± 0.2
49 to 51
59 to 61
48 to 52
58 to 62
- -
- -
Power
Consumption
18 VA maximum (90 to 264 Vac)
12 VA maximum (24 Vac/dc)
Input Accuracy
± 0.20 % of span typical (± 1 digit for display)
Field calibratable to ± 0.05 % of span typical
15-bit resolution typical
CE Conformity
Special Conditions
(Europe)
Shielded twisted pair cables are required for all analog I/O, process
variable, RTD, thermocouple, dc millivolt, low level signal, 4-20 mA, digital
I/O, and computer interface circuits.
* The maximum rating only applies up to 40 °C (104 °F). For higher temperatures, the RH
specification is derated to maintain constant moisture content.