Configuration
12/00 UDC3300 Basic Model: DC33XB User Manual 27
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
INP ALG1
Input 1 Algorithm
ATTENTION
All Input
Algorithms operate in
engineering units except
feedforward which
operates in percent of
output units.
PV or RSP source in the
Control Set Up group must
be set to IN AL1.
NONE CARB C
W AVG CARB D
F FWRD FCC
FFWDMu DEW PT
CARB A OXYGEN
CARB B
NONE
MATH K
Weighted Average Ratio or
K Constant for Math
Selections
0.001 to 1000 floating - -
CALC HI
Calculated Variable High
Scaling Factor for Input
Algorithm
999. to 9999. floating
(in engineering units)
- -
CALC LO
Calculated Variable Low
Scaling Factor for Input
Algorithm
999. to 9999. floating
(in engineering units)
- -
ALG1 INA
Input Algorithm 1
Input A Selection
INP 1
INP 2
LP1OUT
IN AL1
- -
ALG1 INB
Input Algorithm 1
Input B Selection
INP 1
INP 2
LP1OUT
IN AL1
- -
ALG1 INC
Input Algorithm 1
Input C Selection
NONE
INP 1
INP 2
LP1OUT
IN AL1
- -
PCT CO
Percent Carbon Monoxide 0.020 to 0.350 (fractional
percent of CO)
0.200
ALG1BIAS
Input Algorithm 1 Bias -999 to 9999 floating (in
engineering units)
0.000