Section 11 - W7220 JADE™ Economizer Module
135 Honeywell Economizers 63-8594-02
Downloading the software:
1. Download PC tool software from
www.customer.honeywell.com/
economizertools to your personal
computer.
NOTE: OEM and Field tools are the same
hardware but use different programs
and are used for different purposes.
The password for the Field software is:
password. For the OEM password call
your Honeywell OEM representative.
a. During initial
software installation
make sure to check the box to create a
desktop shortcut and check on "Install/
Remove TUSB Drivers" on the
installation screen.
b. If you are repeating installation of the
software or not sure if the TUSB
drivers are on the computer you are
using, follow the steps in 4 below.
c. If you do not want to run the application
immediately, unselect the "Run
JADE™ Configuration tool" before
clicking on FINISH.
d. After successfully downloading the
software to your computer you will
need to restart your computer. Close
all programs and restart your
computer.
e. For additional instructions contact your
local distributor or the Honeywell
hotline at 888-516-9347.
2. Connect W7220-PCMOD interface
module to your computer using the USB
cable provided.
3. Connect W7220-PCMOD tool to your
S-Bus device using 2 non-polarity 18-22
gauge wires and power the Sylk device.
Start configuration tool. If you get a
message stating PC-tool cannot get
firmware revision, then follow the steps in
4 below. The wires can be up to 100 feet
without protection and up to 200 feet
using twisted pair wire.
4. To verify the correct port on your
computer:
Press the Windows key and the Pause
key at the same time on your keyboard.
Click Device Manager that appears on
the left side of the screen (if using
Windows XP the System properties
window will appear; click on hardware,
then device manager).
Click Ports from Device window pop up.
Note the Com port assigned to
TUSB3410. Close the Device Manager
screen.
5. Go to configuration tool and choose the
matching comport to TUSB3410 from the
Settings menu.
For Specific instructions refer to the Honeywell
E- learning module at:
www.customer.honeywell.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Design and Application and is the answer not in the manual?

Honeywell Design and Application Specifications

General IconGeneral
BrandHoneywell
ModelDesign and Application
CategoryController
LanguageEnglish

Related product manuals