E-MON CLASS 3200 METER
13 62-0397—02
6.2 Main Power Board Connections
1. Installing a temporary ground for ESD protection: With all circuits de-ener-
gized, connect a temporary protective earth ground connection for ESD
protection. Prior to performing any unit wiring, be sure to discharge any
static on your person.
2. Installing the E-Mon Class 3200 protective earth ground: Connect an earth
ground wire to the E-Mon Class 3200 (Type 1 enclosure) protective earth
ground lug with a torque of 7 N-m.
WARNING
Failure to attach the protective earth ground wire securely to the meter
creates a potential shock hazard. Do not loosen or remove the screw
securing the ground lug.
Fig. 5. Main Power Board Connections.
62-0397_C.fm Page 13 Wednesday, May 9, 2018 9:28 AM