EasyManuals Logo

Honeywell E-Mon Class 3200 User Manual

Honeywell E-Mon Class 3200
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
E-MON CLASS 3200 METER
62-0397—02 16
6.3 Phasing of Line Voltage
The 3-phase AC power input or single phase option must be in proper phase
sequence. If the sequence is incorrect or a phase is missing, there will be a
message on the meter’s display: “PH Sequence Error” or “PH Missing:. (Refer to
the section on Line Voltage Diagnostics if this message is present.) When the line
voltage is connected correctly, the meter’s display will be blank (no message.)
Wait for the 4-line meter display to scroll to the voltage display. Verify that the
meter reads correct voltages on all three phases. Repeat Step 6.2.4F.
Once the meter displays the correct line voltages and there are no error
messages, you are ready to connect the current sensors to the meter. Before
continuing with the installation, verify that the six screens display as follows:
Screen 1 (kWh): Should read 0.0 kWh; if not, should be
reset.
Screen 2 (kW Peak Demand): kW peak should read 0.0 kW. There will not
be a date/time stamp yet. If there is a kW
peak recorded, it should be reset later.
Screen 3 (kW Load): Should read 0.0 kW load.
Screen 4 (Amps per Phase): There should be 0.0 on all three phases. Or
in the Single Phase option - 0.0 in A and B
phases.
Screen 5 (Volts RMS Phase to Neutral): See the section 6.2.4.F.
Screen 6 (Volts RMS Phase to Phase): See the section 6.2.4.F.
Screen 7 (Power Factor Per Phase): There should be 0.0 PF on all three phases.
Or in the Single Phase option - 0.0 in A and
B phases.
NOTE: The meter will be reset later via the software during “startup” procedures.
62-0397_C.fm Page 16 Wednesday, May 9, 2018 9:28 AM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell E-Mon Class 3200 and is the answer not in the manual?

Honeywell E-Mon Class 3200 Specifications

General IconGeneral
BrandHoneywell
ModelE-Mon Class 3200
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals