E-MON CLASS 3200 METER
15 62-0397—02
6.2 Main Power Board Connections (continued)
D. Connect the three AC main power wires (Phases A, B and C) to their
respective positions as labeled on terminal block TB1. After all conduc-
tors are connected to each of their respective terminal block positions
and tightened to 7 in-lb, verify that each terminal block screw is securely
fastened by gently tugging on each conductor. Verify that no conductor
wires are frayed or shorting to adjacent terminal block positions. For
single phase connection: connect two ac main power wires to phases a
and b and a jumper wire from b to c - factory installed for the Single
Phase option.
E. Turn ON the AC main power input. The meter display will light up and
scroll through 6 displays. Each display is visible for 5 seconds. Display
screens are as follows:
Screen 1 - Total kilowatt-hours (kWh) consumed
Screen 2 - Peak demand (kW) with date & time stamp
Screen 3 - Actual load (kW)
Screen 4 - RMS Amps
Screen 5 - RMS Volts Phase to Neutral
Screen 6 - RMS Volts Phase to Phase
Screen 7 - Power factor (PF) per phase
F. Verify the voltage readings on Screen 5 using an AC voltmeter. Typical
readings shown below are measured phase to neutral (L-N) for 4 wire
and phase to phase (L-L) for 3 wire. Readings should be +/- 10% of
nominal.
NOTE: Meters are powered by phases A and B. The displayed voltages will be the
measured AC voltage between phases.
Meter Type Nominal Voltage Limits (+/- 10%)
120/208V, 3ø, 4 Wire
120/240V, 1ø, 3 Wire
120V, 1ø, 2 Wire
120 VAC (L-N) 108 to 132 VAC
277/480V, 3ø, 4 Wire
277V, 1ø, 2 Wire
277 VAC (L-N) 249 to 305 VAC
240V, 3ø, 3 Wire 240 VAC (L-L) 216 to 264 VAC
400V, 3ø, 4 Wire
(380V, 400V, 415V)
230 VAC (L-N) 207 to 253 VAC
480V, 3ø, 3 Wire 480 VAC (L-L) 432 to 528 VAC
600V, 3ø, 4 Wire (WYE
only)
347 VAC (L-N) 312 to 380 VAC
62-0397_C.fm Page 15 Wednesday, May 9, 2018 9:28 AM

Related product manuals