Venturi-Air Duct Kit
FB 798349 / 04.13 29
10.4 Mounting Î Venturi tubes between 600 mm and 2800 mm
To mount the air duct (with or without the optional mounting kit Part No. 781449) with a pipe length of more than
600 mm the air duct must be drilled at two points as shown in the figure.
Mounting information!
Drill a hole ( 38mm) in the air duct and deburr the
borehole.
upper hole
Î 38 mm
bottom hole
Î 50 mm
Cut the Venturi tube to the required length
(refer Section 10.5 „Adapt the Venturi tube length“).
Seal the borehole of the air duct on the lower end of
the Venturi tube with the supplied plastic gasket
(use only Part No. 781447 / 781448).
Insert rubber gasket in the lower borehole of the air
duct ( 50 mm).
Close the end of the Venturi tube by means of
the supplied sealing cap (Venturi tubes between
600 mm and 2800 mm only).
air duct diameters between 600 mm and 2700 mm
Because ot its lenght, the Venturi tube has to be
supported in the opposite side of the air duct.
Hole
50
mm
Direction of
air flow
Hole
38 mm
30
The Venturi tube should not protrude by more than
30 mm above the air duct.
Fig. 13: Venturi tubes between 600 mm and 2800 m
The Venturi tube must be about 30 mm longer as the diameter of the air duct.
Observe distance caused by the optional mounting kit if required!
Refer to section 10.6 “Mounting the Venturi tube”!