Venturi-Air Duct Kit
FB 798349 / 04.13 37
14 Specifications
Air duct detector housing (Part No. 781443)
Terminals : 1.5 mm² max.
Air velocity : 1 m/s to 20 m/s
Ambient temperature : -10 °C to +60 °C
Storage temperature : -15 °C to +65 °C
Protection class : IP 54
Housing : ABS plastic
Colour : grey (with transparent cover)
Weight : approx. 800g (without detector / detector base)
Dimensions (W x H x D) : 180 x 235 x 183 (mm)
Optional:
Detector base (Part No. 805590)
Detector base with relay contact (Part No. 805591)
Ambient temperature : -20°C to +72°C
Storage temperature : -25°C to +75°C
Terminals : 0.6 mm ∅ to 2 mm
Housing : ABS plastic
Colour : white (similar to RAL 9010)
Weight : approx. 60 g
Dimensions (with detector) : Ø 117 mm, H = 62 mm
Special Specification for Detector base with relay contact (Part No. 805591)
Relay : dry contact, N.O / N.C. configurable with soldering gap
Contact rating : max.
30 V DC / 1A
Max. Current : 5 μA (without detector, relay activated)
Base unit output : Activated with each detector alarm. Further configuration with customer
data settings at the FACP.
IQ8Quad OT
blue
-LKM (Part No. 802379)
Operating voltage : 9 V DC to 42 V DC
Quiescent current @ 19 V DC : 50 μA
Quiescent current @ FACP
Accu
: 0,20 mA @ 27,5 V / 0,28 mA @ 42 V
Alarm indicator : red LED, flashing
Air velocity range : 1 to 3.936 ft/min.
Ambient temperature : -20 °C to +50 °C
Temperature, storage : -25 °C to +75 °C
Ambient humidity : ≤ 95% relative humidity
(non-condensing)
IP rating : IP 43 (with base + option)
Housing : ABS plastic
Colour : white (similar to RAL 9010)
Weight : approx. 110 g
Dimensions (with base) : Ø 117 mm, H = 62 mm
Detector specification : EN 54-7:2006 / -17:2005, CEA 4021
VdS approval : G 207128
CE certificate : 0786 - CPD - 20116
For further information refer to fire detector manual.
Venturi tube
Part No. 781446 781447 781448
Length (mm) 600 1500 2800
Weight (g) 200 600 1200
Material aluminium