HC900 Control System Architectures - HC900 controller Features 
Revision 1.9    HC900 Process & Safety Controller Safety Manual  15 
01/14 
HC900 controller Features 
Hardware 
• 
Modular rack structure; components are ordered individually as needed 
• 
CPU with Ethernet communications 
• 
Easy to assemble, modify, and expand 
• 
Local (C30S) and Remote input/output racks (C50S/C70S), private Ethernet-linked sub-network 
• 
Parallel processing - a microprocessor in each I/O module performs signal processing, to preserve update 
rates and proper failsafe action on loss of Controller updates. 
• 
Power supplies - provide power to CPU rack and Scanner I/O rack 
Redundancy (this will be available with the next release) 
• 
Redundant C75S CPU 
• 
Redundancy Switch Module (RSM) – required between redundant CPUs 
• 
Redundant Power Supply – provides redundant power to any CPU rack or Scanner2 I/O rack 
• 
Power Status Module (PSM) – required when using a second power supply in Scanner2 I/O rack 
Communications 
All CPUs (except where noted): 
• 
Two galvanic isolated RS-485 serial ports. 
• 
RS-485 port used for 2-wire link to HMI or field devices with port configuration as Modbus RTU master 
or slave. 
• 
Ethernet 10/100Base-T connection to: up to 5 PC hosts via Modbus/TCP protocol, Peer-to Peer 
communication with other HC900 Controllers for process applications, and the Internet. C70S has 2 
Ethernet ports for connection to up to 10 PC hosts. It also supports Modbus/TCP Initiator function over 
both ports. 
• 
Private Ethernet 100Base-T connection to I/O expansion racks (except C30S CPU) 
Redundancy (this will be available with the next release) 
• 
Supervisory Network – Ethernet 10/100 baseT to PC Applications (Designer & HC Utilities), 
communicates to peer HC900 Controllers over Ethernet for process applications.  C75S has two 
Ethernet ports. Lead C75S CPU supports up to 10 concurrent sockets. It also supports Modbus/TCP 
Initiator function over both ports. 
• 
I/O Network – Direct connection to each C75 CPU. 
• 
Device Network –Isolated RS-485 Serial Interface; Modbus RTU. Two serial ports available. Each port 
can be set as Modbus Master or Slave. Host Serial Interface for Honeywell or third party operator 
interface