HC900 Control System Fault Detection and Response - HC900 Controller Diagnostics
Revision 1.9 HC900 Process & Safety Controller Safety Manual 59
01/14
Safety related modules
Modules diagnostics are scanned every fast or normal scan interval depending on the application
configuration. When a fault if detected a diagnostic is reported and the associated function blocks fault pin
is asserted. Output modules are driven to their failsafe state either under controller direction or detection of
a loss of communication to its controller or scanner. The failsafe time out of communication loss with an
IO module is three scan cycles. Controller application will continue to execute based upon the applications
configuration.
HC900 Controller Diagnostics
HC900 Controller diagnostics can be found in “HC900 Process Controller Installation and User Guide” 51-52-25-
107.
HC900 SIL Compatibility
Model Number Description Process/ Safety
Applications
Notes
900R04-0200 4 Slot Rack Process & Safety
900R08-0200 8 Slot Rack Process & Safety
900R12-0200 12 Slot Rack Process & Safety
900R08R-0200 8 Slot Rack w/ redundant
Power
Process & Safety
900R12R-0200 12 Slot Rack w/ redundant
Power
Process & Safety
900RR0-0101 Redundant Controller
Rack
Process & Safety
900P01-0101 120/240 VAC. 60W Process
900P02-0101 120/240 VAC, 28 W Process
900P24-0101 24 VDC, 60 W Process
900P01-0201 120/240 VAC. 60W Process & Safety
900P02-0201 120/240 VAC, 28 W Process & Safety
900P24-0201 24 VDC, 60 W Process & Safety
900PSM-0101 Redundant Power status
module
Process & Safety
900RSM-0101 Redundant Switch module Process & Safety
900C30S-0360-00 C30 Controller Process & Safety No Scanner